Demagnetization Method for Reducing Inrush Current of Single Phase 1 kVA Transformer

I Made Yulistya Negara, Dicky Wahyu Darmawan, Ryan Nurdianto, Dedet Candra Riawan, Arif Musthofa, Dimas Anton Asfani, Mochammad Wahyudi, Daniar Fahmi

Abstract


This study deals with an effort to reduce inrush current of single phase transformer during its energizing. Inrush current affected by residual flux was minimized using demagnetization method in order to reduce residual flux trapped in the core of transformer. Two methods of demagnetization namely variable frequency-constant voltage (VFCV) and variable voltage–constant frequency (VVCF) were applied and the effectiveness of both methods were then compared. Both methods were supplied with alternated direct current (DC), however the one was changed its frequency and the other one was changed its voltage. The results obtained after transformer was demagnetized using these methods show that VFCV method educed inrush current up to 76%, on the other hand VVCF ethod reduced inrush current only up to 37%. Moreover, demagnetization time process of VFCV method was about 1.46 s, which is 1 s faster than VVCF method.


Keywords: demagnetization; inrush current; variable voltage-constant frequency; variable frequency-constant voltage


Full Text:

PDF

References


K. Baris, L. d. Francisco, C. Dariusz, Z. Zivan, and B. Leo, “Mitigation of Inrush Currents in Network Transformers by Reducing the Residual Flux with an Ultra-Low-Frequency Power Source”, IEEE Trans. Power Del., vol. 26, no. 3, pp. 1563 – 1570, July. 2011.

F. de Leon, Ashkan Farazmand, Saeed Jazebi, Digvijay Deswal, dan Raka Levi, “Residual Flux in Transformer by Application of an Alternating Polarity DC Voltage Source”, IEEE Transactions on Power Delivery, Vol. 30, no. 4, August 2015.

H. Brunke and K. J. Frohlich, “Elimination of Transformer Inrush Currents by Controlled Switching. I. Theoretical Considerations”, IEEE Trans. Power Del., vol. 16, no. 2, pp. 276–280, April. 2001.

H. Brunke and K. J. Frohlich, “Elimination of Transformer Inrush Currents by Controlled switching. II. Application and Performance Considerations”, IEEE Trans. Power Del., vol. 16, no. 2, pp. 281–285, April. 2001.

P. C. Y. Ling and A. Basak, “Investigation of magnetizing inrush current in a single-phase transformer”, IEEE Trans. Magn., vol. 24, no. 6, pp. 3217–3222, Nov. 1988.

F. de León, A. Farazmand, and P. Joseph, “Comparing the T and Pi Equivalent Circuits for the Calculation of Transformer Inrush Currents”, IEEE Trans. Power Del., vol. 27, no. 4, pp. 2390–2398, October. 2012.

M. Jamali, M. Mirzaie, and S. Asghar Gholamian, “Calculation and Analysis of Transformer Inrush Current Based on Parameters of Transformer and Operating Conditions”, ISSN 1392-1215 ©2011

Firmansyah Mokhamad, IGN Satriyadi, Soedibjo, “Studi Perbandingan Metode Pengurangan Arus Inrush pada Transformator Daya 500 kV GITET Krian”, Jurnal Teknik Pomits, vol. 1, no. 1, pp. 1 – 6, 2014.




DOI: https://doi.org/10.12962/j25796216.v1.i1.4

Refbacks