This paper deals with ferroresonance detection on an transmission line utilizing wavelet transform. The ferroresonance involving linear capacitor and non-linear inductor was triggered by the disturbances of power system, such as lightning strike, switching operation and ground fault. The primary voltage of capacitive voltage divider (CVT) was observed as response of the triggered ferroresonance. The voltage signal was processed using wavelet daubechies (db5) until 9 levels. The cyclic cumulative energy for each condition was then calculated and compared. The result shows that the cyclic cumulative energy ratio and duration of period of cumulative energy deviation can be used as ferroresonance detection parameters.Keywords: ferroresonance; capacitive voltage divider, wavelet transform

Biografi Penulis

I Gusti Ngurah Satriyadi Hernanda, Institut Teknologi Sepuluh Nopember

Department of Electrical Engineering

I Made Yulistya Negara, Institut Teknologi Sepuluh Nopember

Department of Electrical Engineering

Adi Soeprijanto, Institut Teknologi Sepuluh Nopember

Department of Electrical Engineering

Dimas Anton Asfani, Institut Teknologi Sepuluh Nopember

Department of Electrical Engineering

Mochammad Wahyudi, Institut Teknologi Sepuluh Nopember

Department of Electrical Engineering

Surya Dwi Kisdarmawan, Institut Teknologi Sepuluh Nopember

Department of Electrical Engineering

Daniar Fahmi, Institut Teknologi Sepuluh Nopember

Department of Electrical Engineering

Referensi

Elmo Price, “A Tutorial on Ferroresonanceâ€, ABB Inc.

Ferraci, P., “Ferroresonanceâ€, Group Schneider: Cahier no 190, pp. 1-28, 1998

A.H.A. Bakar, “Analysis of Lighting-caused Ferroresonance in Capasitor Voltage†Ekivier 2011 Electrical Power and Energy System33 pp 1536-1541

Siavash Beheshtaein, “Application of Wavelet-base Method and DT in Detection of Ferroresonance from other Transient Phenomenaâ€, International Symposium on Innovations in Intelligent Systems and Applications, IEEE 2012

Zhang Bo and LU Tiecheng, “On The Use of Wavelet Decomposition for Ferroresonance Detection in Power Systemâ€, Asia-Pacific Power and Energy Engineering Conference, IEEE 2009

G. Mokryani, et.al. “Wavelet Based Kernel Fisher Classifier For Ferroresonance Identificationâ€, International Conference on Intelligent System Applications to Power Systems, IEEE 2009

J. A. C. Araujo, “Modeling and Analysis of Power Transformers under Ferroresonance Phenomenonâ€, Universitat Rovira I Virgili, Tarragona, 2015

Huang Chun-Wei, Jyh-Cherng Gu, Ming-Ta Yang, “Applying Wavelet Transform to Ferroresonance Detection and Protectionâ€, ICECECE 2014